Campbell-scientific CR1000 Measurement and Control System Manual do Utilizador Página 346

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 345
Section 8. Operation
346
Command 13 Copies the specified program to the designated drive and sets
the run attribute of the program to Run Always. Data on a CF card from the
previously running program will be erased.
Command 14 Copies the specified program to the designated drive and sets
the run attribute to Run Now. Data on a CF card from the previously running
program will be erased.
Example Power-up.ini Files
Powerup.ini Example
'Code format and syntax
'Command = numeric power-up command
'File = file associated with the action
'Device = device to which File is copied. Defaults to CPU:
'Command,File,Device
13,Write2CRD_2.cr1,cpu:
Powerup.ini Example
'Copy program file pwrup.cr1 from the external drive to CPU:
'File will run only when CR1000 powered-up later.
2,pwrup.cr1,cpu:
Powerup.ini Example
'Format the USR: drive
5,,usr:
'
Powerup.ini Example
'Load an operating system (.obj) file into FLASH as the new OS.
9,CR1000.Std.04.obj
Powerup.ini Example
'A program file is carried on an external USB: drive.
'Do not copy program file from USB:
'Run program always, erase data.
13,toobigforcpu.cr1,usb:
Powerup.ini Example
'Run a program file always, erase data.
13,pwrup_1.cr1,cpu:
Powerup.ini Example
'Run a program file now, erase data now.
14,run.cr1,cpu:
Vista de página 345
1 2 ... 341 342 343 344 345 346 347 348 349 350 351 ... 587 588

Comentários a estes Manuais

Sem comentários