CS11-L Current Transformer
TABLE 6-1. Max Amps on Each of the Range Codes in the Datalogger (one pass only).
Datalogger >>>
Range Codes
(mV)
CR200(X)
Series
CR10X
CR500
CR510
CR1000
CR800
CR850
CR21X CR23X CR3000
Amperage
Resolution
2.5 0.5 0.5 0.000133
5 1 0.000067
7.5 1.5 1.5 0.000400
10 2 0.000133
15 3 0.000200
20 4 0.000134
25 5 5 0.001334
50 10 10 10 0.000666
200 40 40 0.002660
250 50 50 0.013340
500 100 0.006660
1000 200 200 0.013320
2500 125 200 200 0.133400
5000 200 200 200 200 0.066600
6.1 CR800, CR850, CR1000, or CR3000 Programming
With these dataloggers, the best method for monitoring amperage is to make
millivolt burst measurements, and then calculate rms. The millivolt burst
measurements are made by using the VoltSE instruction with multiple reps on
the same channel (for example, negative value for channel number). The
SpaDevSpa instruction calculates rms.
Program must be run in the pipeline mode on CRBasic
dataloggers.
NOTE
It is important to measure complete cycles. If 100 measurements are taken
during a 0.1 second time period, the result will be five complete cycles for a 50
Hz waveform or six complete cycles for a 60 Hz waveform.
Do not average the waveform reading in the data table nor
use the 60 Hz or 50 Hz noise rejection in the measurement
instructions in the program. Doing so would result in an
incorrect zero amperage reading.
CAUTION